S-Series Detector Head

Contact us for a quote here

FeaturesS-Series Detector Head

  • Explosion proof housing
  • Patented water repellent sensor coating
  • Available for LEL, H 2 S, CO, O 2 , and ppm HC
  • IR sensors available for LEL & CO2
  • Long life sensors (2 + years typical)
  • Competitively priced

Applications

  • Petrochemical plants
  • Refineries
  • Offshore Drilling Platforms
  • Water & wastewater treatment plants
  • Pulp & paper mills
  • Gas, telephone, & electric utilities
  • Parking garages
  • Manufacturing facilities
  • Steel
  • Automotive
  • Chemical storage buildings

The RKI “S” series gas sensor/transmitters are highly reliable and very cost effective basic 4-20 mA transmitters for detection of common gas hazards. The “S” series transmitters are available for LEL, Oxygen, H2S, CO, or for 0 - 500 ppm Hydrocarbon detection (for various fuels or solvents). The electronics are encased inside a potted package to avoid damage from mechanical abuse or corrosion, and the amplifier is installed inside an explosion-proof enclosure. Sensors for LEL, H2S, CO, and ppm HC are explosion-proof with flame arrestors. The Oxygen sensor utilizes an internal I.S. barrier, so all 5 versions are designed for use in hazardous atmospheres.

The only tools required to calibrate the “S” series are a voltmeter, screwdriver, and cal gas. The zero and calibration functions are performed by adjusting potentiometers on the amplifiers. The amplifier has test jacks for connection of a voltmeter for calibration purposes, and the sensor response is viewed on the voltmeter as a 100mV to 500mV signal. Field calibration can be performed easily and quickly by one person.

The “S” series transmitters can be used either indoors or outdoors. The flame arrestors utilize a patented coating which makes them water repellent, and splash guards are also available for use in very wet environments.

The transmitter operates from 24 VDC (10.5VDC to 30 VDC), and provides a 4-20mAsignal which can be connected to a wide variety of controllers.


Part # LEL
65-2400RK
O2
65-2504RK
H2S
65-2422RK
Min Operating
Voltage
11 VDC
Max Operating
Voltage
30 VDC
Max Current
Draw
200 mA
(power wires)
25 mA (signal wires)
3 or 4 wires
25 mA
(2 wire system)
Signal Output 4 mA at 0% LEL
20 mA at 100% LEL
4 mA at 0 % Oxygen
20 mA at 25%
Oxygen
4 mA at 0 ppm H2S
20 mA at 100 ppm
H 2 S
Response
Time
30 seconds to 90%
of concentration
20 seconds to 90%
of concentration
45 seconds to 90% of concentration
Operating Environment
Location Indoor or outdoor.
Explosion proof for
Class , Div. 1,
Groups B, C, and D.
Indoor or outdoor.
Explosion proof
housing and
intrinsically safe sensor.
Indoor or outdoor.
Explosion proof for
Class , Div. 1,
Groups B, C, and D.
Temperature -40 to 185° F 30 to 120° F 0 to 120° F
Humidity 0 - 99% RH,
non condensing
Housing Aluminum Explosion
proof enclosure
Sensor
Type Catalytic
Combustion
Galvanic Cell Electrochemical
Life Expectancy 1 to 2 years normal service when
intermittently exposed to
flammable gas in air mixtures
2 years normal service 2 years normal service when intermittently exposed to H2S
Controls
Sensor Current Factory set and sealed -
Zero Sets transmitter output to
4 mA with 0%LEL
output from combustible sensor
Sets transmitter output to 4 mA with an inert gas (zero) output from O 2 sensor Sets transmitter output to 4 mA with zero output from H2S sensor
Span Sets transmitter out-
put to 20 mA with
100% LEL output
from combustible sensor
Sets transmitter output to 17.44 mA with 21% VOL O 2 (fresh air) output from O 2 sensor Sets transmitter output to 20 mA with 100 ppm output from H2S sensor
Tools Needed Screwdriver and voltmeter used to make adjustments



Part # CO
65-2432RK
HC
65-2460RK
Min Operating
Voltage
11 VDC
Max Operating
Voltage
30 VDC
Max Current
Draw
25 mA
(2 wire system)
100 mA
(power wires) 25 mA (signal wires) 3 wires
Signal Output 4 mA at 0 ppm CO
20 mA at 500 ppm CO
4 mA at 0 ppm 20 mA at 500 ppm
Hexane. Linear.
Response
Time
30 seconds to 90% of concentration
Operating Environment
Location Indoor or outdoor. Explosion proof for Class I, Div. 1, Groups B, C, and D. Explosion proof for Class ,
Div. 1, Groups B, C, and D.
Temperature 0 to 120° F 30 to 120° F
Humidity 0 - 99% RH, non condensing 5 - 95% RH, non condensing
Housing Aluminum Explosion proof enclosure
Sensor
Type Electrochemical Metal Oxide
Semiconductor
Life Expectancy
2 to 3 years normal service 5 to 10 years typical
Controls
Sensor Current - Factory set and sealed
Zero Sets transmitter output to 4 mA with zero output from CO sensor Sets transmitter output to 4 mA with zero ppm output from sensor
Span Sets transmitter output to 20 mA with 500 ppm output from CO sensor Sets transmitter output to 20 mA with 500 ppm Hexane (typical) output from sensor
Tools Needed Screwdriver and voltmeter used to make adjustments
Part # CO2
65-2391RK-03
CH4
65-2390RK-CH4
HC
65-2390RK-HC
Measuring Range 0-5% Vol. 0-100% LEL
Max Current
Draw
60 mA (power wires)
25 mA (signal wires) 3 wires
Signal Output 4 - 20 mA signal
Response
Time
30 seconds to 90% of concentration
Operating Environment
Location Indoor or outdoor. Explosion proof for Class I, Div. 1,
Groups B, C, and D.
Temperature -4 to 122° F
Humidity 0 - 99% RH, non condensing
Housing Aluminum Explosion proof enclosure
Sensor
Type Infrared
Life Expectancy
5+ years normal service
Controls
Sensor Current - Factory set and sealed
Zero Sets transmitter output to 4 mA with zero output from CO2 sensor Sets transmitter output to 4 mA with 0% LEL output from
combustible sensor
Span Sets transmitter output to 20 mA with 5% volume output from CO2 sensor Sets transmitter output to 20 mA with 100% LEL output from
combustible sensor
Operating Voltage
11 VDC to 30 VDC
Approvals
C CSA US
Warranty
One year materials and workmanship

 

 

 