RM-580
- Wide variety of detectable gases and detector heads
- Easy to read 3 color LED bar graph display
- Sample draw or diffusion type sensor heads
- Peak gas concentration hold function
- 2 Alarm levels with relays
- Integrated compact design with easy plug-in type modules
- Wide range of combustible gases detected in both PPM or % LEL ranges
- Auto-ranging from PPM to % LEL available
- Built in alarm test mode
- Auto zero function, auto cal function for % LEL & oxygen
- 4-20 mA output signal
- Wall mount or rack mount designs
- Petrochemical plants
- Refineries
- Chemical Plants
- Semiconductor
- Gas, Power, and Water Utilities
- Iron and Steel Works
The RM-580 system is available in either a 4, 6, 9, or 12 channel wall mount housings making it easy to fit custom space requirements. The brilliant three color bar graph display is quick and easy to read even from long distances. The RM-580's display changes colors, from green to orange to red, when the alarm set points are activated. For system flexibility, a built-in output signal of 4-20 mA can be used to interface with your existing Programmable Logic Controllers, (PLC). The RM-580 is compatible with the widest range of detector heads. Detector heads can be either diffusion or sample drawing style which will ensure the most accurate delivery of samples given your particular facility or application. The RM-580 system is available in either a 4, 6, 9, or 12 channel wall mount housings making it easy to fit custom space requirements. The brilliant three color bar graph display is quick and easy to read even from long distances. The RM-580's display changes colors, from green to orange to red, when the alarm set points are activated. For system flexibility, a built-in output signal of 4-20 mA can be used to interface with your existing Programmable Logic Controllers, (PLC). The RM-580 is compatible with the widest range of detector heads. Detector heads can be either diffusion or sample drawing style which will ensure the most accurate delivery of samples given your particular facility or application.
Power Requirements |
115 VAC and 24 VDC with 230 VAC optional |
Sampling Method |
Accepts both diffusion and sample drawing type detector heads |
Operating Conditions |
0 - 122 • F, 10 - 90% RH, non-condensing |
Enclosure Type |
Metal module |
Mounting Style |
Wall mount for 4, 6, or 12 modules |
Display Method |
3 color LED bar graph (52 segments) |
Alarms |
2 per module, 2 common relays, external reset |
Alarm Indication |
1st alarm flashing LED (orange), latched,
continuous light when reset 2nd alarm flashing LED (red), latched mode |
Output Signal |
4-20 mA DC |
Audible Alarm |
Enclosure mounted buzzer, 94 dB at 1' Coded output: pulsing = gas alarm, steady = fail |
Sensor Inputs |
Any 4-20 mA transmitter, 24 VDC, 2 or 3 wire, 250 mA max standard. LEL or Oxygen sensors direct connect. |
Warranty |
One year materials and workmanship |
Partial List Of Detectable Gases
Many other gases or ranges available. Contact RKI for gases or ranges not listed
Ammonia (NH3) |
0 - 75.0 ppm |
| Arsine (AsH3 ) | 0 - 0.20 ppm |
| Boron Trichloride (BCl3) | 0 - 15.0 ppm |
| Carbon Dioxide (CO2) | 0 - 1.0 % |
| Carbon Monoxide (CO) | 0 - 300 ppm |
| Chlorine (Cl2) | 0 - 3.0 ppm |
| Chlorine Dioxide (ClO2) | 0 - 1.00 ppm |
| Chlorine Trifluoride (ClF3) | 0 - 1.00 ppm |
| Combustibles | 0 -100% LEL |
| Diborane (B2H6) | 0 - 30.0 ppm |
| Fluorine (F2) | 0 - 6.0 ppm |
| Hydrogen (H2) | 0 - 2000 ppm |
| Hydrogen Chloride (HCl) | 0 - 15.0 ppm |
| Hydrogen Fluoride (HF) | 0 - 9.0 ppm |
| Hydrogen Sulfide (H2S) | 0 -100.0 ppm |
| Nitric Oxide (NO) | 0 -100.0 ppm |
| Nitrogen Dioxide (NO2) | 0 - 15.0 ppm |
| Nitrogen Trifluoride (NF3) | 0 - 30.0 ppm |
| Oxygen (O2) | 0 - 25.0 % |
| Ozone (O3) | 0 - 1.0 ppm |
| Phosphine (PH3) | 0 - 1.0 ppm |
| Silane (SiH4) | 0 - 15.0 ppm |
| Sulfur Dioxide (SO2) | 0 - 30.0 ppm |
| TEOS (Si(OC2H5)4) | 0 -15/30 ppm |